Generac

Undervoltage

Generator output voltage too low. Faulty AVR, overload, or worn brushes/slip rings.

Code 1900 / 1902
Undervoltage

Need a technician? Skip the troubleshooting — open a service ticket and we'll handle it.

Safety first

⚠ SAFETY FIRST: Disconnect battery (negative lead first) before inspecting internal components. Never work on a generator that may auto-start.

Overview

What 1900 / 1902 means

Generator output voltage too low. Faulty AVR, overload, or worn brushes/slip rings.

Faulty or failed Automatic Voltage Regulator (AVR)

Generator overloaded — exceeding rated kVA/kW capacity

Worn or dirty brushes / slip rings on the alternator

Failed excitation winding in the rotor

Incorrect controller firmware or AVR parameter settings

Heavy capacitive or inductive load causing voltage sag

Loose connections on output terminals or transfer switch

Step-by-step workflow

Follow the diagnostic and reset sequence

1

Check Output Voltage with a Meter

CHECK

Use a multimeter to measure actual output voltage at the generator's output terminals or transfer switch. Compare to the nameplate rated voltage (typically 120/240V).

Below 100V on a 120V system = significant undervoltage. Check both legs (L1 and L2) on a 240V system. An imbalance between legs can indicate a winding or connection issue. Record the voltage readings for your service report.
2

Check Connected Load

CHECK

An overloaded generator will produce low voltage as the alternator struggles to supply demand. Shed all non-essential loads and check if voltage recovers.

If voltage rises to normal when load is removed — generator is overloaded. Keep total load below 80% of rated kW. If voltage remains low with no load — AVR or alternator issue is suspected.
3

Inspect Brushes & Slip Rings

ACTION

Worn brushes that no longer make good contact with the slip rings reduce excitation current, causing output voltage to drop. This is especially common on units with 500+ hours.

With generator OFF and battery disconnected, access the brush assembly at the alternator end. Brushes should extend at least 1/4 inch from the holder. Slip rings should be smooth and clean. Clean slip rings with a lint-free cloth. Replace brushes if worn.
4

Test the AVR

ACTION

The Automatic Voltage Regulator (AVR) maintains constant output voltage. A failed AVR is one of the most common causes of persistent undervoltage on a running generator.

AVR testing requires a voltmeter and knowledge of excitation voltage — this is typically a technician-level test. If brushes and load are confirmed normal but voltage is still low, the AVR is the primary suspect. Contact A&A Power Generators for AVR testing and replacement.
5

Clear Fault & Test

RESET

If load was the cause, clear the alarm and restart with a reduced load profile.

Evolution: Press OFF/Reset. Nexus: Press OFF → Enter. Monitor output voltage with a meter during the restart. It should stabilize at rated voltage within 10–15 seconds.
Evolution Controller
Evolution Controller
Nexus Controller
Nexus Controller

After reset

Did the code clear?

Yes — code cleared

The code cleared and the unit returned to standby. Log the incident, confirm ready-to-run status, and monitor the next exercise cycle.

No — code returned

If the code returns immediately, stop resetting and move into service. The issue likely needs inspection of wiring, switches, or a controller-level component.

Need direct help?

Move from troubleshooting into the right support path.

Use the same workflow page to open a ticket, book service, or route into a broader consultation if the issue needs parts, diagnostics, or scheduling.

Prevention

Best practices and next checks

Annual Brush & Slip Ring Inspection

Brushes wear gradually. Annual inspection prevents a surprise voltage failure during an outage.

Stay Within Rated Capacity

Never exceed 80% of rated kW for sustained operation. Overload is the fastest way to destroy an AVR.

Get a Maintenance Plan

A&A Power Generators inspects the AVR, brushes, and output voltage at every maintenance visit. 888-991-4500

Update Controller Firmware

Outdated firmware can cause false undervoltage trips. Keep your controller updated.

Enable Mobile Link Alerts

Receive Undervoltage warnings immediately via the Generac Mobile Link app.

Load Test Annually

Have a technician perform a full-load voltage test annually to confirm AVR and alternator health.

Get a Maintenance Plan

Let A&A Power Generators handle all preventative maintenance for your generator.

Still need help?

A&A Power can take it from here.

If the issue persists after following the workflow, route the unit into ticket, appointment, or consultation support so the team can take over with the right service path.